Recommendation 50: Approach to fire and explosion protection
From The Public Inquiry into the Piper Alpha Disaster, published 12 November 1990.
Recommendation
The regulations and related guidance notes should promote an approach to fire and explosion protection:- (i) which is integrated as between - — active and passive fire protection — different forms of passive fire protection, such as fire insulation and platform layout, and — fire protection and explosion protection (paras 19.87-95); (ii) in which the need for, and the location and resistance of, fire and blast walls is determined by safety assessment rather than by regulations (para 19.96); (iii) in which the function, configuration, capacity, availability and protection of the fire water deluge system is determined by safety assessment rather than by regulations (paras 19.97 and 19.99); (iv) which facilitates the use of a scenario-based design method for fire protection as an alternative to the reference area method (paras 19.91 and 19.98); and (v) which provides to a high degree the ability of the fire water deluge system, including the fire pump system, to survive severe accident conditions (para 19.100).
Government response
No government response to this recommendation is on the record yet.